Study: Determination of the equivalent thermal conductivity coefficient for PScoat (Katodesk-tech, Katowice) – full text
Title: Determination of the equivalent thermal conductivity coefficient for the thermoreflective paints – layers
Author(s): Mag. Ing. Philip Skuczeń, Mag. Ing. Kamil Kotarski, Katodesk-tech, Ul. Św. Jana 11/4, 40-012 Katowice
Certified translation from Polish: Łukasz Brzana, state-sworn interpreter and translator for the German language (register number TP/86/14), deed register no. 322/2022, Lublin, 14.03.2022
Length: 9 pages (original deed and translation)
Faithful English text version of the certified German translation of the Polish original. The original PDF is authoritative: pscoat-ersatz-waermeleitfaehigkeitskoeffizient-studie-de.pdf
Note on classification: Historical figure λ = 0.00012 W/(m·K) = d/R_system with R_system = 2.493 m²K/W at 0.35 mm – see calculation on page 7. Correct statement today: R_system(d) = R0 + d/λ_mat + ΔRse_max·(1 − e^(−d/d0_se)) + ΔR_rad_max·(1 − e^(−d/d0_rad)), non-linear. Material λ 0.0324 W/(m·K) fits SINTEF 0.02–0.0519 W/(m·K). The following text is the faithful version of the document.
Certified translation from Polish. [Translator’s notes are given in brackets.] Every page of the original deed additionally carries the letterhead „Katodesk-tech, Ul. Św. Jana 11/4, Katowice 40-012“ in the page footer; this recurring letterhead is not repeated on every page here.
Determination of the equivalent thermal conductivity coefficient for the thermoreflective paints – layers
In accordance with the technical conditions to be achieved in the year 2022, the Ministry of Transport, Construction and Maritime Economy has drafted a regulation to which buildings and their location should conform.
Among other things, this draft specifies the requirements regarding the insulation of building partition walls that newly constructed and modernised buildings must meet. One of the requirements is the reduction of the heat transfer coefficient U, which is very important, as this entails a change in the thickness of the insulation that must be used.
Currently the heat transfer coefficient for walls U must be lower than the value: 0,2 W/(m²K). In practice this means that the wall must be covered with a conventional insulation material with a thickness of approximately 25 cm.
Looking at previous years: 2014 – Umax= 0,25 W/(m²K), 2017 – Umax= 0,23 W/(m²K), a trend towards lowering the maximum value of the coefficient U is observed, and thus an increase in the thickness of the insulation. These changes significantly affect the increase in investment costs.
Investors‘ measures focus on increasing thermal insulation by applying additional partitions to building walls, made of materials with low thermal conductivity coefficients, for example: glass wool mats, polystyrene boards, as well as thermally reflective materials.
The technology of technically reflective protection is based on limiting heat transport between environments with different temperatures by way of infrared radiation. In this field, one of the most modern solutions is the application of thermally reflective paint layers, which are characterised by a high reflection coefficient of infrared radiation, reaching 98 %. The reflection of this radiation towards the heat source with the higher temperature creates on the reflective surface a so-called heat barrier with a much higher effectiveness than classic thermal insulation materials.
A thermally reflective layer manufactured on the Polish market is PScoat. It is used for interior and exterior painting as well as for roof coverings. Thermally reflective PScoat compounds are widely used in industry as insulation for pipelines, tanks, silos, etc.
Heat transfer between environments of different temperatures at the level of infrared radiation and of heat conduction can be understood by means of an equivalent heat conduction mechanism, subject to the existing, measured thermal conductivity coefficient of the thermally reflective coating.
The test is based on creating climatic conditions closest to those prevailing in winter: outside temperature -15 °C as well as +20 °C in the inhabited room. The purpose of the test is to determine how the application of thermally insulating PScoat layers affects heat transfer through the test partition wall.
[Page 1]
Description of the test procedure
The tests were carried out on the test partition wall in the following variants:
- Plasterboard on both sides – without application of the PSC system
- Plasterboard on both sides – coated with the PSC system on the cooled side
- Plasterboard on both sides* on the cooled side: polystyrene with a thickness of 10 cm without application of the PSC system
- Plasterboard on both sides – coated with the PSC system on the cold side as well as with the paint that is an element of the PSC system
Figures
PARTITION WALL – Version GK; PARTITION WALL – Version PSC; PARTITION WALL – Version ST10; PARTITION WALL – Version PSC+PSC paint.
Samples for the test
PSC insulation system
- Base
- Thermal layer
- PSC facade paint
All elements of the system are water-dilutable products. The total thickness of the system’s layer is 0,35 mm, and the thickness of the PSC paint itself is 0,1 mm.
[Page 2]
Power consumption test
Test purpose
The purpose of the test is to determine the influence of the application of products from the PSC series on the power consumption required to maintain the temperature in the warm zone – a simulation of the savings achieved thanks to the application of products from the PSC series.
Conditions and description of the test
The test was based on maintaining the average temperature in the warm (20 °C) and cold (-15 °C) zone for 24 hours. Stable thermal conditions were established in both simulator zones, which were subsequently maintained for a total period of 24 hours. The costs of maintaining the temperature in the cold zone were not measured – stability of the outside conditions was assumed, whereas the costs of the power consumption required to maintain the temperature in the warm zone were the subject of the present test. The measurements of power consumption and temperature were carried out using the devices described in point no. 2 of Annex no. 1 to the report.
Test result
Below, the test results are presented in tabular form as well as as a diagram. The savings between the individual partition wall versions were recorded in the absolute dimension – relating the value of the saving to the base partition wall.
| Partition wall version | Consumption within 24 h [kW] | Saving |
|---|---|---|
| GK | 6,58 | – |
| PSC | 4,38 | 33,43 % |
| ST10 | 4,48 | 31,91 % |
| PSC+PSC paint | 4,08 | 37,99 % |
Table 2 Power consumption test results. Fig. 6 Power consumption diagram – savings in absolute terms. [Page 3]
Determination of the equivalent lambda coefficient for the PScoat system
1. Assumptions
- a. Wall dimensions: 2,19 m x 2,19 m,
- b. The test environment is constant throughout all tests.
- c. The only variable between the tests is the partition wall.
- d. Lambda for polystyrene: 0,044 [W/m²*K]
- e. Heating efficiency: 1
[Page 4]
2. Known
- a. Thermal resistance of the control partition wall: Ro= 2,826 [m²*K/W]
- b. Thermal resistance of the polystyrene-insulated partition wall: R1= 5,098 [m²*K/W]
- c. Temperature difference between the environments: ΔT = 35 °K
- d. Amount of electrical energy supplied to the test environments: Qo = 6580 Wh; Q1 = 4480 Wh; QPSC,1 = 4380 Wh; QPSC,2 = 4080 Wh
- e. Area of the tested wall: P = 4,796 m²
- f. Thickness of the PScoat thermal insulation layers: d = 0,00035 m
3. Description of the method for the equivalent lambda coefficient for the PScoat insulation system
Knowing the above values, we determine the value of the heat flow that passed through the control wall [Qo‘]. Assuming that the difference in power consumption results exclusively from the change introduced in the obstacle, we determine the value [Qo‘] on the basis of the ratio of the thermal resistances of the control partition wall and the partition wall with polystyrene.
Knowing the value of the heat flow for the control partition wall and the difference in power consumption, we can on this basis determine the thermal resistance of the partition walls insulated with the PScoat system. In order to verify the correctness of the calculations, we use this method to determine the resistance for the polystyrene-insulated partition wall.
4. Calculations
Determination of the heating system’s efficiency
ς = ΔQ‘ / ΔQ
where: ς – heating system efficiency [%]; ΔQ‘ – difference of the calculated heat flows between the control partition wall and the partition wall insulated with 10 cm of polystyrene; ΔQ – difference in power consumption in the tests of the control partition wall and the partition wall insulated with 10 cm of polystyrene.
ΔQ = Qo – Q1 = 2100 Wh
ΔQ‘ = Qo‘ – Q1′ = (1/Ro – 1/R1) * 24h * 4,796 m² * 35°K
[Page 5]
ΔQ‘ = 635,617 Wh
ς = 635,617 Wh / 2100 Wh = 0,303
Determination of the energy losses of the control partition wall in the total energy consumption of the environment
1/Ro = Qi‘
1/R1 = Qi‘ – ΔQ
0,354 = Qi‘
0,196 = Qi‘ – 2100 Wh
Qi‘ = 4704,43 Wh
Determination of the thermal energy of the control partition wall taking into account the efficiency of the heating system
Qi = Qi‘ * ς = 1 425,44 Wh
Determination of the equivalent thermal resistance for the partition wall insulated with PScoat
Q1′ = Qi‘ – (Qo – QPSC,1) = 4704,43 Wh – 2200,00 Wh = 2504,43 Wh
Q1“ = Q1′ * ς = 758,03 Wh
Total heat flow for the whole partition wall for 1 h: Q“1h1 = Q1“/24h = 31,584 W
Total heat flow for 1 m² of the polystyrene-insulated partition wall: Qs,0,1 = Q’1h1/P = 31,584 W / 4,796 m² = 6,585 W/m²
Determination of the heat transfer coefficient for the partition wall insulated with the PScoat system: UPSC,1 = Qs,0,1/ΔT = 6,585 W/m² / 35°K = 0,188 W/(m²*K)
Determination of the thermal resistance for the partition wall insulated with the PScoat system: RPSC,1 = 1/UPSC,1 = 5,319 m²*K/W
[Page 6]
Determination of the equivalent thermal resistance for the same PScoat partition wall
RPSC = RPSC,1 – Ro
R*PSC = 5,319 m²*K/W – 2,826 m²*K/W = 2,493 m²*K/W
Determination of the equivalent lambda coefficient for the Pscoat insulation system
λ*PSC = d / RPSC
where: d – thickness of the PScoat insulation = 0,00035 m
λ*PSC = 0,00035 m / 2,493 m²*K/W = 0,00014 W/(m²+K)
Determination of the equivalent thermal resistance for the partition wall insulated with PScoat + PScoat interior
Q2′ = Q1′ – (Qo – QPSC,2) = 4704,43 Wh – 2500,00 Wh = 2204,43 Wh
Q2“ = Q2′ * ς = 667,23 Wh
Total heat flow for the whole partition wall for 1 h: Q“1h2 = Q2“/24h = 27,81 W
Total heat flow for 1 m² of the polystyrene-insulated partition wall: Qs,0,2 = Q’1h2/P = 27,81 W / 4,796 m² = 5,797 W/m²
Determination of the heat transfer coefficient for the partition wall insulated with the PScoat system: UPSC,2 = Qs,0,1/ΔT = 5,797 W/m² / 35°K = 0,166 W/(m²*K)
[Page 7]
Determination of the thermal resistance for the partition wall insulated with the PScoat system: RPSC,2 = 1/UPSC,2 = 6,038 m²*K/W
Determination of the equivalent thermal resistance for the same PScoat partition wall
R*PSC,2 = RPSC,2 – Ro
R*PSC,2 = 6,038 m²*K/W – 2,826 m²*K/W = 3,215 m²*K/W
Conclusions
According to the above calculations, the equivalent resistances for the PScoat and PScoat+PScoat interior insulation systems exceed the resistance of polystyrene with a thickness of 10 cm and λ = 0,044 W/(m*K).
The results are as follows:
Resistance Pscoat: R*PSC = 2,493 m²*K/W
Resistance PScoat+PScoat interior: R*PSC,2 = 3,215 m²*K/W
Thermal conductivity coefficient PScoat λPSC: λPSC = 0,00012 W/(m*K)
Thermal conductivity coefficient PScoat+PScoat interior λPSC,i: λPSC,i = 0,000416 W/(m*K)
Notes
No thermal conductivity coefficient was determined for the PScoat insulation system, as this test was carried out for an insulation with a thickness of 0,00035 m.
Increasing its thickness does not guarantee a linear improvement of the thermal parameters of the partition wall.
[Page 8]
Conclusion and certification
The report was prepared by:
Mag. Ing. Philip Skuczeń
Mag. Ing. Kamil Kotarski
Katodesk-tech,
Ul. św. Jana 11/4
Katowice 40-012
[Long stamp reading:] Energy certificates of building structures, Mag. Ing. Philip Skuczeń, św. Jana 11/4, 40-012 Katowice, NIP [tax ID]: 634-277-81-54 registration number: 15211, [illegible signature]
[Long stamp reading:] [Logo] KATODESK, Kamil Kotarski, 40-012 Katowice, ul. Św. Jana 11/4, NIP [tax ID] 9542769121 REGON [company ID] 365497762, [illegible signature]
Annex no. 1: Test report.
I, Łukasz Brzana, state-sworn interpreter and translator for the German language, entered in the register of state-sworn interpreters and translators kept by the Minister of Justice under number TP/86/14, hereby certify the conformity of the translation with the original deed in the Polish language submitted to me. The deed comprises nine pages. The translation was likewise prepared on nine pages.
Deed register no.: 322/2022. Lublin, 14.03.2022.
[Page 9]